We have written twice about the wave of attacks on refrigeration systems: when French supermarkets were hit, and when Romania's DNSC confirmed six stores. Both articles answered the same question, what is confirmed and what to check. On 6 November something different appeared: a measurement.
Unit 42, the research arm of Palo Alto Networks, counted internet-exposed devices made by the manufacturers listed in the CERT-FR advisory. The result for 5 and 6 November: more than 5,000 across Europe. And for France, where the attacks began, it published the trend across three periods. That is the part a board can use, because it is the first number in this whole story that you can watch fall.
The figures Unit 42 published
- More than 5,000 internet-exposed devices made by the companies listed in the CERT-FR advisory, identified across 5 and 6 November 2026.
- France, exposed devices by period: 1,853 between 1 and 15 October, 558 between 16 and 31 October, 316 between 1 and 6 November. A decline of roughly 83% against the first period.
- The first wave, overnight on 11 to 12 October, primarily targeted approximately 700 supermarkets in France, according to Unit 42. BleepingComputer reported 250 to 350 French stores for the same period. Aggregate figures differ by source.
- The second wave, overnight on 1 to 2 November, expanded across at least 10 additional European countries, affecting 100 to 115 retail locations, according to Unit 42. BleepingComputer names Belgium, the Netherlands, Sweden, Luxembourg, Ireland and Estonia, with more than 115 stores.
- Temperatures raised as high as 50 degrees Celsius, and in some cases fires, according to Unit 42.
- Unit 42's explicit caveat about its own measurement: the presence of an exposed device does not necessarily mean it runs a vulnerable software version that could have been exploited.
Why the French decline is the only number that matters here
An exposed device is not a compromised device, and Unit 42 says so plainly. But exposure has a property compromise does not: it can be counted, it can be counted from the outside, and it can be counted again next month.
France went from 1,853 to 316 in five weeks. The report does not say who took what off the internet, and the decline cannot be attributed to any single measure. The CERT-FR advisory, public pressure, supplier intervention and simply closing the interfaces all acted together. The direction, however, is unambiguous, and it shows what happens when an entire country checks the same class of equipment at the same time.
The rest of Europe is, for now, on the other side of that comparison. More than 5,000 devices remained exposed in early November, after both waves and after the national advisories.
At France's blood service the chain has three links, not one
On 2 November, the Établissement français du sang reported that temperature and defrost thresholds had been raised to extremely high levels in three of its cold-storage facilities. It lost no blood products. Monitoring and alarm systems flagged the change, staff fixed the equipment or transferred the products, and collection and distribution continued. EFS is working with ANSSI and the Ministry of Health.
The new part arrived on 4 November. EFS stated it was not the direct target: its refrigeration equipment supplier was. And that supplier, Coolworld Rentals, confirmed an incident involving remote monitoring software and added a sentence worth reading twice: "The vulnerability currently being reported in the media relates to a component from a third-party supplier and was outside Coolworld's direct control."
Read as a liability diagram, that sentence describes three links: the institution that holds the blood, the supplier that runs its cold chain remotely, and the supplier of a component inside that supplier's software. Your own supplier register almost certainly stops at the second. The question to ask at contract renewal is not "do you have security?" but "which third-party components run in the platform you use to reach our equipment, and how do you find out when one of them has a vulnerability?".
What five US agencies asked for on 5 November
CISA, the FBI, Health and Human Services, the Department of Agriculture and the Department of Transportation jointly published a fact sheet on activity targeting industrial refrigeration and cold chain monitoring systems. The sectors named are Healthcare and Public Health, Chemical, Food and Agriculture, and Transportation Systems. The possible impacts listed are temperature change, fire hazards, loss of inventory and changes to the service life of the system.
The four measures in the joint fact sheet
- Remove control system devices and systems from the internet.
- Change default passwords and strengthen passwords.
- Apply patches and keep devices and systems updated.
- Identify, retire and replace legacy devices the vendor no longer supports.
- The inclusion test was stated by Chris Butera, CISA's Acting Executive Assistant Director for Cybersecurity, in a single sentence: "Every organization that depends on refrigeration and monitoring systems should assume it could be a target." It is not the equipment list that puts you on the list. It is the dependency.
The vulnerabilities have names. The vector does not.
- In advisory ICSA-25-140-03, CISA published three vulnerabilities in the Danfoss AK-SM 8xxA series: CVE-2025-41450, improper authentication that could result in an authentication bypass, in versions prior to R4.2; CVE-2025-41451, command injection through alarm-to-mail configuration fields leading to post-authenticated remote code execution, in versions prior to 4.3.1; and CVE-2025-41452, a denial of service, prior to 4.3.1.
- Fixes exist: R4.2 for the first, 4.3.1 for the other two. The vulnerabilities were reported by Tomer Goldschmidt of Claroty Team82.
- The advisory also states that no known public exploitation specifically targeting these vulnerabilities has been reported to CISA. That sentence dates from the 26 August 2025 revision, more than a year before this wave. It is not evidence either way.
- The initial access vector in this wave remains unconfirmed. Unit 42 notes widespread speculation that affected devices were running vulnerable software versions or using manufacturer default credentials, but presents it explicitly as speculation.
- Sabcobel, a Belgian refrigeration company, said the November attackers exploited the same vulnerability used in October in France. That is a supplier's statement, not an authority's finding.
The metric you can report monthly
- The numerator: how many of your refrigeration controllers, of any brand, answer from a public IP address. Not how many should answer, but how many do.
- Who measures it: someone outside the team that administers the equipment. If the administrator reports their own exposure, the number will always be zero.
- How to measure it when the equipment belongs to the supplier: ask in writing for the list of public addresses and ports through which remote access happens, plus the model and the firmware version read off the device, not the one displayed on the login page.
- The target: zero devices reachable directly from the internet, with remote access only through a VPN or protected network. France showed that a decline of more than 80% is achievable in five weeks.
- The second metric, for unsupported equipment: how many units in your estate no longer receive security updates from the manufacturer, and what replacement date each one has in the budget. For these there is no patch, so the state cannot be "updated", only "isolated" or "replaced".
- Reporting deadlines, if you fall within NIS2 scope: early warning within 24 hours, incident notification within 72 hours, final report within one month of the notification. Establish before an incident whether the obligation is yours or the supplier's who runs the installation, because the answer changes who calls whom at 01:30.
What remains unconfirmed
- Who did it. On 3 November the pro-Russian hacktivist groups NoName057(16) and Z-Pentest claimed responsibility via Telegram posts, according to Unit 42. The claims remain unverified.
- How large the first wave was. Approximately 700 French supermarkets according to Unit 42, and 250 to 350 according to BleepingComputer. There is no consolidated official figure.
- How high the temperature went at the blood service. One outlet reported 110 degrees Celsius; EFS speaks of extremely high levels, without a figure. We have used the institution's wording.
- Whether the French decline in exposure is permanent or only a temporary withdrawal of interfaces until public attention moves on.
- Whether the three Danfoss CVEs were actually used in this wave. No authority has confirmed that.
Sources and verification
Open the original sources for context, updates and the exact wording of claims.
- 01Unit 42 (Palo Alto Networks) — Turning Up the Heat: Inside the Attacks on Europe's Refrigeration System, Matt Brady și Jared Valentine, 6 noiembrie 2026
- 02CISA, FBI, HHS, USDA și DOT — comunicat și fișă informativă privind sistemele industriale de refrigerare și de monitorizare a lanțului de frig, 5 noiembrie 2026
- 03CISA — avizul ICS ICSA-25-140-03, Danfoss AK-SM 8xxA Series (Update A), revizuit pe 26 august 2025
- 04BleepingComputer — atacul asupra sistemelor de refrigerare pentru stocarea sângelui în Franța, declarațiile EFS și Coolworld, 4 noiembrie 2026
- 05CERT-FR — alerta CERTFR-2026-ALE-012, 12 octombrie 2026, actualizată pe 13 octombrie
- 06Directiva (UE) 2022/2555 (NIS2) — articolul 21 alineatul (2) litera (d) privind securitatea lanțului de aprovizionare și articolul 23 alineatul (4) privind termenele de raportare